Drycooler rental - Dry cooler unit 837 kW


Our dry-coolers are frequently used to cool water that is heater than the ambient air by heat exchange. Dry-cooler rental is ideal for providing a cost-effective air cooling solution for high temperatures.


PERFORMANCE
ReferenceDRYTB CIAT
Power dissipated during summerkW837
Air inlet / outlet temperature°C+30/+42
Water inlet / outlet temperature°C+45/+40
Airflowm3/h150 333
Power dissipated during winterkW4 153
Air inlet / outlet temperature°C+10/+65
Water inlet / outlet temperature°C+80/+60
Water flow ratem3/h71.78
HYDRAULICS
Camlock Hydraulic ConnectionØDN100
PumpEXTENSION
FluidWATER
ELECTRICAL
IntensityA27
Power supply V400 V TRI +T
Power cable sectionmm²5g6
PHYSICALS
Dimensionsmm9,800 x 2,400 x 1,400
Empty weightkg3 000
Noise level at 10 metresdB (A)53