Mixed steam boiler room flow rate 10 T/H - 7 MW
To meet your specific requirements, Tibbloc offers complete boiler rooms in containers, with 24/72-hour SPHP operation. EQUIPMENT
- WEB ACCESS (Remote supervision access on subscription)
- Chimney
Compact skid-mounted boiler with 2H fireproof unit - Electric start burner without assistance.
Standard gas pressure 300 mb (possibility to provide expansion 1 to 4 bar).
CE Boiler mixed GAS 300 mb or FOD high pressure and in compliance with the current regulation on atmospheric emissions.
Large water volume boiler, which offers high steam quality for specific uses.
It ensures stable operation between low and high loads and adaptation to load variations.
SIZE AND WEIGHT | ||
---|---|---|
Length x Width x Height | mm | 12 000 x 3200 x 3500 |
Empty weight | kg | 30 000 |
Loaded weight | kg | 46 000 |
TECHNICAL DATA | RGL 70/2-A ZM-3LN | |
Steam flow rate | kg/h | 10 000 |
Maximum allowable pressure | Bar | 25 |
Maximum operating pressure | Bar | 22 |
Starting temperature | °C | 220 |
Return air temperature | °C | 200 |
Fuel | Gas or FOD | |
GAS consumption | Nm3/h | 750 |
FOD consumption | L/h | 540 |
Recommended oil tank | m3 | 20 |
Operating mode | APHP or SPHP | 24/72H |
2H Fireproof unit | Feet | 10 |
Feed pumps | CONNECTIONS | Variable flow rate |
CONNECTIONS | DN50 PN10/16 | |
Steam start-up | DN150 PN40 | |
Gas supply | kW | DN100 PN10 |
Start and return ES | V Tri | DN 250 PN40 |
Fuel loop | A | 2" X 2 BSP |
Processed water | DN50 PN10 | |
Evacuation | DN40 PN10 | |
Valve event | Kg | DN80 PN10 |
Power supply | kW | 55 |
Voltage | 400v TRI + N | |
Intensity | A | 130 |
Including heating | kW | 5.5 |