Generator rental cooling 10 kW


Efficient and reliable cooling – The GFT10 chiller is the most compact chiller in the Tibbloc range.

It can be used in various installations, for process cooling or air conditioning. The GFT10 delivers a nominal power of 6.6 kW for a chilled water outlet temperature range of +7°/+12°C.

For other applications, please consult the Tibbloc integrated project planning unit.

Environmentally friendly – The GFT10 uses R410A refrigerant for reliability and optimum efficiency.
Low noise – The GFT10 is a low noise unit, 52 d(B)A at 10 metres.


Robust construction for rental


Easy and quick to install and implement


Wide operating range for various applications


Environmentally friendly refrigerant



PERFORMANCE
ReferenceGFT10 MTA
CompressorTYPICAL SET-UP1 scroll
Nominal powerkW6.6
kcal/h5675
Chilled water outlet temperature°C+7/+12
HYDRAULICS
Flow rate for dT of 5°cm3/h1.7 m3/h / 30 mCE
Glycol water system°C-10°/-5°C
Max. water outlet temperature°C+15
Nominal ambient temperature°C+35
RefrigerantR410A
Camlock Hydraulic ConnectionLDN25
Start controlConstant
Camlock Hydraulic ConnectionØDN25
PumpIntegrated
ELECTRICAL
Nominal currentA7
Electrical powerkW3.8
Power supply A400 V TRI +T
Power cable sectionmm²5G 6²
GeneratorskVA10
PHYSICALS
Sizemm1250x560x810
Tare weightkg450
Noise level at 10 metresdB (A)52