Rental of air coolers low-temperature 100 kW
The 10 kW, 50 KW and 100 KW TIBBLOC low-temperature coil rental is a chiller solution with 3-way control valve and automatic defrost for temporary cooling applications in operating ranges from -8°C to +10°C.
THE BENEFITS OF RENTING
24/7 on-call
Choice of lease term
Without fixed capital investment
TECHNICAL DATA | EVAB50 | EVAB100 |
Reference | 54 kW | LU-VE 100 |
Nominal power | kW | 100 |
Fan air flow rate | m3/h | 76 600 |
T°C Inlet / outlet | °C | -8 / -4 |
Ambient T°C | °C | 2 |
Brine flow rate | m3/h | 24.6 |
Internal volume | l | 116 |
Fluid | Mono propylene | MPG 30% |
ELECTRICAL | 400 V TRI +T | 400 V TRI +T |
Ventilation power | kW / A | 6.7 kW / 14.8 A |
Defrosting power | kW / A | 53 kW/ 76 A |
Power supply | V | 400 V TRI +T |
Power cable section | mm² | 2x5g35 |
Electrical connection | Plug | P17 125 A |
Camlock hydraulic connections | Ø | DN50 |
SIZE | 56 db(a) | 52 db(a) |
Noise level at 10 metres | dB (A) | 60 |
Size | mm | 6,000 x 1,300 x 1,500 |
Weight | kg | 1 000 |