Mixed boiler room rental 1T/h


The Tibbloc mixed boiler room is equipped with :

  • Sample cooler
  • SPHP 24H operating mode controller
  • Water treatment with DUPLEX softener
  • Feed water tank
  • Cooled blowdown vessel
  • Continuous TH monitoring

Optional :TIBBVIEW supervision with remote web access (alarms, temperatures, pressures and status)


THE ADVANTAGES OF RENTING


24/7 on-call


Choice of rental period


Without fixed capital investment


PERFORMANCE
Steam flow ratekg/h1000
Maximum allowable pressurebar15
Maximum operating pressurebar13
BurnersmbarRiello
Gas pressuresmbar300
GAS consumptionNm³/h95
FOD consumptionl/h70
Recommended fuel tank5 to 10
Operating modeSPHP 24H/72H
Feed water tankl2000
Food pumps x 2
CONNECTIONSDN65 PN16
Steam start-upDN100 PN40
Gas supplyDN65 PN16
Customer buffer tank inletDN50 PN16
Fuel loop3/4" x 2 BSP
Untreated waterkWDN32 PN10/16
Condensate returnsVDN50 PN10/16
EvacuationADN80 PN10/16
Power supplykW13
VoltageV400 V tri
IntensityA32
PHYSICALSkg14 000
Sea container unitFeet30
Dimensionsm9.50 x 2.40 x 3.36
Chimney height from groundm6
Empty weightkg12 000