Suitable for any type of rental
Regulated start of fixed start
Fuel boiler house hire
Turnkey standalone solutions, including fuel delivery*.
Quick to implement, simple to position (free choice of the location), our fuel boiler houses are delivered, installed and commissioned by our teams.
*on-demand fuel delivery
Typical set-up :
- 1 or 2 boilers (from 63 to 5 000 kW)
- Fuel burner
- Surge tank
- Primary pump + recycling pump
- Electrical boardroom, safety controls, regulation
- Isolation valve
- Stainless steel fireplace
- Large flow trap
- Constant start or regulated start with 3-way valve, depending on the model

KW capacity | kcal/hr | Electrical connections | Genset kVA | Fluid connections | Pump design flow | Surge tank Liter | Start | Max. fuel consumption Ltr/hr | Dimensions Length x width x Height in mm | Weight | Sound pressure @10 meters dB (A) |
63 | 54 180 | 220V + N + T 16A | 30 | DN 50 PN 10/16 | 2,9 m3/hr @4 mCE | 11 | Fixed | 6 | 2200x1500x2350 | 800 | 35 |
150 | 129 000 | 220V + N + T 16A | 30 | DN 50 PN 10/16 | 4 m3/hr @5 mCE | 35 | Regulated | 15 | 2200x1300x1750 | 800 | 35 |
190 | 163 400 | 220V + N + T 16A | 30 | DN 50 PN 10/16 | 8,2 m3//hr @5 mCE | 35 | Regulated | 19 | 3050x2450x2600 | 2100 | 40 |
230 | 197 800 | 400V TRI + N + T 16A | 30 | DN 50 PN 10/16 | 11 m3//hr @11 mCE | 50 | Regulated | 23 | 3540x2460x2600 | 2000 | 43 |
290 | 249 400 | 400V TRI + N + T 16A | 30 | DN 80 PN 16 | 12,5 m3/hr @5 mCE | 100 | Fixed | 30 | 3050x2450x2900 | 2300 | 43 |
300 | 260 580 | 400V TRI + N + T 16A | 30 | DN 50 or 80 | 13 m3/hr @10 mCE | 100 | Regulated | 30 | 3050x2450x2900 | 2300 | 43 |
300 CF2H | 283 800 | 400V TRI + N + T 16A | 30 | DN 50 or 80 | 15 m3/hr @10 mCE | 150 | Regulated | 30 | 3050x2450x2900 | 2300 | 43 |
330 | 283 800 | 400V TRI + N + T 16A | 30 | DN 50 or 80 | 15 m3/hr @10 mCE | 150 | Regulated | 30 | 3050x2450x2901 | 2300 | 43 |
530 | 455 800 | 400V TRI + N + T 20A | 30 | DN 80 PN 10/16 | 24 m3/hr @10 mCE | 200 | Regulated | 53 | 6050x2450x2900 | 4300 | 46 |
548 | 471 280 | 400V TRI + N + T 20A | 30 | DN 80 PN 10/16 | 23,5 m3/hr @10 mCE | 250 | Regulated | 55 | 6050x2450x2900 | 4300 | 46 |
600 CF2H | 516 000 | 400V TRI + N + T 20A | 30 | DN 80 PN 10/16 | 26 m3/hr @10 mCE | 300 | Regulated | 60 | 6400x2450x2600 | 7200 | 42 |
610 | 523 740 | 400V TRI + N + T 20A | 60 | DN 80 PN 10/16 | 26,2 m3/hr @13,4 mCE | 300 | Regulated | 61 | 6050x2450x2900 | 5700 | 46 |
1 000 | 860 000 | 400V TRI + N + T 20A | 60 | DN 80 PN 10/16 | 45 m3/hr @14,7 mCE | 500 | Regulated | 105 | 6300x2450x2600 | 8 000 | 44 |
1 050 | 903 000 | 400V TRI + N + T 20A | 60 | DN 80 PN 10/16 | 45 m3/hr @14,7 mCE | 500 | Regulated | 105 | 6050x2450x2900 | 7000 | 50 |
1 466 | 1 260 760 | 400V TRI + N + T 32A | 60 | DN100 PN 10/16 | 63 m3/hr @10 mCE | 400 | Regulated | 146 | 6050x2450x2901 | 8000 | 55 |
1 850 | 1 591 000 | 400V TRI + N + T 32A | 60 | DN100 PN 10/16 | 77 m3/hr @12 mCE | 600 | Regulated | 185 | 6050x2430x2600 | 7500 | 55 |
1 990 | 1 711 400 | 400V TRI + N + T 32A | 60 | DN100 PN 10/16 | 85,5 m3/hr @10 mCE | 500 | Regulated | 199 | 6050x2450x2900 | 7500 | 56 |
1990 CF2H | 1 711 400 | 400V TRI + N + T 32A | 60 | DN100 PN 10/16 | 85,5 m3/hr @10 mCE | 500 | Regulated | 199 | 6600x2800x2900 | 9450 | 49 |
2 200 | 1 892 000 | 400V TRI + N + T 32A | 60 | DN 150 PN 10/16 | 94,6 m3/hr @10 mCE | 1200 | Regulated | 220 | 6050x2450x2900 | 9600 | 58 |
3 000 | 2 580 000 | 400V TRI + N + T 50A | 100 | DN 150 PN 10/16 | 130 m3/hr @10 mCE | 1200 | Regulated | 300 | 6050x2460x2900 | 9800 | 58 |
3 550 | 3 053 000 | 400V TRI + N + T 50A | 125 | DN 150 PN 10/16 | 160 m3/hr @10 mCE | 1200 | Regulated | 355 | 6050x2460x2600 | 10000 | 59 |
5 000 | 4 300 000 | 400V TRI + N + T 50A | 125 | DN 150 PN 10/16 | 215 m3/hr @10 mCE | 1200 | Regulated | 500 | 9200x3130x3450 | 18000 | 62 |
7000 hydro unit | 400V TRI + N + T 160A | DN 150 and DN 200 PN 16 | 360 m3/hr @40 mCE | no | Fixed | 3050x2430x2600 | 2600 |
Our range of fuel tanks
Equipment that comply with the highest safety standards
You can choose to hire the fuel tank that is right for you and benefit from a large autonomy with storage capacities from 2 000 to 20 000 liters.

Fuel tank capacity Liter | Type | Dimensions Length x width x Height mm | Weight Kg (empty) |
5000 | Double wall aerial | 3600x1500x1800 | 1 400 |
10 000 | Double wall aerial | 4200x2000x2300 | 2 200 |
20 000 | Double wall aerial | 5050x2450x3000 | 3 900 |
3 000 ADR | Double wall and 110% retention | 2320x1550x1320 | 1 000 |
5 000 | Double wall and 110% retention | 2300x2300x2450 | 2 930 |
10 000 (a) | Double wall and 110% retention | 2300x2300x2450 | 2930 |
10 000 (b) | Double wall and 110% retention | 3250x2250x2450 | 2100 |
2 000/2 500 Ltrs containerized fuel tanks
Integrated in a thick galvanized steel retention tank, our 2000 and 2500 liter fuel tanks are protected against possible shocks and vandalism.
Technical features
- Heavy gauge galvanized steel unit (3 mm)
- Slings for forklift
- Galvanized tilting and padlockable steel lid
- HDPE fuel tank with metal reinforcements to NF standards
- Filling cap
- Oil filter with isolation valve
- Police valve
Aerial fuel tanks on cradles
5000/10 000/20 000L
Our oil tanks on cradles are all equipped with a double wall, in accordance with the current regulations.
Technical characteristics
- Double wall class A steel tank, conforming to standard NF.EN-12285-2
- Optional leak detector
- Manhole equipped
- Sitting on cribs
- Lifting ring
- Pneumatic gauge
- Easy ground connection
- Push / pull fuel / flow connection
- Filling at the height of man
Fuel tanks in containers 5,000 / 10,000 Liters
Our fuel tanks, up to 10,000 Ltrs, are integrated into an ISO 20′ lockable container. Only authorized personnel can access it, which protects fuel, an increasingly expensive resource.
Technical features
- ISO 20′ container with locking
- Double wall tank, in accordance with the current regulations.
- Easy to move with slings or forklift.
- Door opening from outside as inside, with anti panic bar
- Aluminum sheet flooring
- Double wall class A steel tank, conforming to standard NF.EN-12285-2
- Optional leak detector
- Manhole equipped
- Pneumatic gauge
- Lighting and ventilation
- 1 indoor electrical outlet
- Electrical installation according to European standards
- Easy ground connection
ADR-compliant 3 000 liters double wall fuel tank
Technical features
- UN (United Nations) certified steel for the transportation of fuel oil on the road according to the ADR regulations,
- Tanks that can be transported full at any place, without need for emptying or degassing,
- Anti wave barriers – 110% retention
Fuel tanks new generation
Technical features
- Double wal steel fuel tank (3 mm)
- Forks in all four directions and lifting rings
- Transportable empty
- 110% Retention capacity
Hoses
- Fuel
- Heating
- District hot water

Diameter | Connection | Length meters | Application |
DN 15 | Push / Pull | 4 or 5 | Boiler house 60 to 1800 KW |
DN 15 | Push / Pull | 10 | Boiler house 60 to 1800 KW |
DN 20 | Push / Pull | 11 | Boiler house 2200 to 3700 KW |
DN 32 | Female input / outputt | 30 | Fuel loop from 5 000 KW |
DN 50 | PN 10/16 | 10 | Boiler house 60 to 230 KW |
DN 80 | PN 10/16 | 10 | Boiler house 290 to 600 KW |
DN 100 | PN 10/16 | 10 | Boiler house 800 to 1200 KW |
DN 150 | PN 10/16 | 5 | Boiler house 1400 to 7000 KW |
DN 150 | PN 10/16 | 10 | Boiler house 1400 to 7000 KW |