solutions fioul

Rental Fuel Boiler House : Our Global Solutions for hire

traitrouge

Suitable for any type of rental
Regulated start of fixed start

Fuel boiler house hire

Turnkey standalone solutions, including fuel delivery*.

Quick to implement, simple to position (free choice of the location), our fuel boiler houses are delivered, installed and commissioned by our teams.

*on-demand fuel delivery

Typical set-up :

  • 1 or 2 boilers (from 63 to 5 000 kW)
  • Fuel burner
  • Surge tank
  • Primary pump + recycling pump
  • Electrical boardroom, safety controls, regulation
  • Isolation valve
  • Stainless steel fireplace
  • Large flow trap
  • Constant start or regulated start with 3-way valve, depending on the model
chaufferie fioul
KW capacity kcal/hr Electrical connections Genset kVA Fluid connections Pump design flow Surge tank Liter Start Max. fuel consumption Ltr/hr Dimensions Length x width x Height in mm Weight Sound pressure @10 meters dB (A)
63 54 180 220V + N + T 16A 30 DN 50 PN 10/16 2,9 m3/hr @4 mCE 11 Fixed 6 2200x1500x2350 800 35
150 129 000 220V + N + T 16A 30 DN 50 PN 10/16 4 m3/hr @5 mCE 35 Regulated 15 2200x1300x1750 800 35
190 163 400 220V + N + T 16A 30 DN 50 PN 10/16 8,2 m3//hr @5 mCE 35 Regulated 19 3050x2450x2600 2100 40
230 197 800 400V TRI + N + T 16A 30 DN 50 PN 10/16 11 m3//hr @11 mCE 50 Regulated 23 3540x2460x2600 2000 43
290 249 400 400V TRI + N + T 16A 30 DN 80 PN 16 12,5 m3/hr @5 mCE 100 Fixed 30 3050x2450x2900 2300 43
300 260 580 400V TRI + N + T 16A 30 DN 50 or 80 13 m3/hr @10 mCE 100 Regulated 30 3050x2450x2900 2300 43
300 CF2H 283 800 400V TRI + N + T 16A 30 DN 50 or 80 15 m3/hr @10 mCE 150 Regulated 30 3050x2450x2900 2300 43
330 283 800 400V TRI + N + T 16A 30 DN 50 or 80 15 m3/hr @10 mCE 150 Regulated 30 3050x2450x2901 2300 43
530 455 800 400V TRI + N + T 20A 30 DN 80 PN 10/16 24 m3/hr @10 mCE 200 Regulated 53 6050x2450x2900 4300 46
548 471 280 400V TRI + N + T 20A 30 DN 80 PN 10/16 23,5 m3/hr @10 mCE 250 Regulated 55 6050x2450x2900 4300 46
600 CF2H 516 000 400V TRI + N + T 20A 30 DN 80 PN 10/16 26 m3/hr @10 mCE 300 Regulated 60 6400x2450x2600 7200 42
610 523 740 400V TRI + N + T 20A 60 DN 80 PN 10/16 26,2 m3/hr @13,4 mCE 300 Regulated 61 6050x2450x2900 5700 46
1 000 860 000 400V TRI + N + T 20A 60 DN 80 PN 10/16 45 m3/hr @14,7 mCE 500 Regulated 105 6300x2450x2600 8 000 44
1 050 903 000 400V TRI + N + T 20A 60 DN 80 PN 10/16 45 m3/hr @14,7 mCE 500 Regulated 105 6050x2450x2900 7000 50
1 466 1 260 760 400V TRI + N + T 32A 60 DN100 PN 10/16 63 m3/hr @10 mCE 400 Regulated 146 6050x2450x2901 8000 55
1 850 1 591 000 400V TRI + N + T 32A 60 DN100 PN 10/16 77 m3/hr @12 mCE 600 Regulated 185 6050x2430x2600 7500 55
1 990 1 711 400 400V TRI + N + T 32A 60 DN100 PN 10/16 85,5 m3/hr @10 mCE 500 Regulated 199 6050x2450x2900 7500 56
1990 CF2H 1 711 400 400V TRI + N + T 32A 60 DN100 PN 10/16 85,5 m3/hr @10 mCE 500 Regulated 199 6600x2800x2900 9450 49
2 200 1 892 000 400V TRI + N + T 32A 60 DN 150 PN 10/16 94,6 m3/hr @10 mCE 1200 Regulated 220 6050x2450x2900 9600 58
3 000 2 580 000 400V TRI + N + T 50A 100 DN 150 PN 10/16 130 m3/hr @10 mCE 1200 Regulated 300 6050x2460x2900 9800 58
3 550 3 053 000 400V TRI + N + T 50A 125 DN 150 PN 10/16 160 m3/hr @10 mCE 1200 Regulated 355 6050x2460x2600 10000 59
5 000 4 300 000 400V TRI + N + T 50A 125 DN 150 PN 10/16 215 m3/hr @10 mCE 1200 Regulated 500 9200x3130x3450 18000 62
7000 hydro unit 400V TRI + N + T 160A DN 150 and DN 200 PN 16 360 m3/hr @40 mCE no Fixed 3050x2430x2600 2600

Our range of fuel tanks

Equipment that comply with the highest safety standards

You can choose to hire the fuel tank that is right for you and benefit from a large autonomy with storage capacities from 2 000 to 20 000 liters.

location cuves fioul
Fuel tank capacity Liter Type Dimensions Length x width x Height mm Weight Kg (empty)
5000 Double wall aerial 3600x1500x1800 1 400
10 000 Double wall aerial 4200x2000x2300 2 200
20 000 Double wall aerial 5050x2450x3000 3 900
3 000 ADR Double wall and 110% retention 2320x1550x1320 1 000
5 000 Double wall and 110% retention 2300x2300x2450 2 930
10 000 (a) Double wall and 110% retention 2300x2300x2450 2930
10 000 (b) Double wall and 110% retention 3250x2250x2450 2100

2 000/2 500 Ltrs containerized fuel tanks

Integrated in a thick galvanized steel retention tank, our 2000 and 2500 liter fuel tanks are protected against possible shocks and vandalism.

Technical features

  • Heavy gauge galvanized steel unit (3 mm)
  • Slings for forklift
  • Galvanized tilting and padlockable steel lid
  • HDPE fuel tank with metal reinforcements to NF standards
  • Filling cap
  • Oil filter with isolation valve
  • Police valve

Aerial fuel tanks on cradles
5000/10 000/20 000L

Our oil tanks on cradles are all equipped with a double wall, in accordance with the current regulations.

Technical characteristics

  • Double wall class A steel tank, conforming to standard NF.EN-12285-2
  • Optional leak detector
  • Manhole equipped
  • Sitting on cribs
  • Lifting ring
  • Pneumatic gauge
  • Easy ground connection
  • Push / pull fuel / flow connection
  • Filling at the height of man

Fuel tanks in containers 5,000 / 10,000 Liters

Our fuel tanks, up to 10,000 Ltrs, are integrated into an ISO 20′ lockable container. Only authorized personnel can access it, which protects fuel, an increasingly expensive resource.

Technical features

  • ISO 20′ container with locking
  • Double wall tank, in accordance with the current regulations.
  • Easy to move with slings or forklift.
  • Door opening from outside as inside, with anti panic bar
  • Aluminum sheet flooring
  • Double wall class A steel tank, conforming to standard NF.EN-12285-2
  • Optional leak detector
  • Manhole equipped
  • Pneumatic gauge
  • Lighting and ventilation
  • 1 indoor electrical outlet
  • Electrical installation according to European standards
  • Easy ground connection

ADR-compliant 3 000 liters double wall fuel tank

Technical features

  • UN (United Nations) certified steel for the transportation of fuel oil on the road according to the ADR regulations,
  • Tanks that can be transported full at any place, without need for emptying or degassing,
  • Anti wave barriers – 110% retention

Fuel tanks new generation

Technical features

  • Double wal steel fuel tank (3 mm)
  • Forks in all four directions and lifting rings
  • Transportable empty
  • 110% Retention capacity

Hoses

  • Fuel
  • Heating
  • District hot water
flexibles
Diameter Connection Length meters Application
DN 15 Push / Pull 4 or 5 Boiler house 60 to 1800 KW
DN 15 Push / Pull 10 Boiler house 60 to 1800 KW
DN 20 Push / Pull 11 Boiler house 2200 to 3700 KW
DN 32 Female input / outputt 30 Fuel loop from 5 000 KW
DN 50 PN 10/16 10 Boiler house 60 to 230 KW
DN 80 PN 10/16 10 Boiler house 290 to 600 KW
DN 100 PN 10/16 10 Boiler house 800 to 1200 KW
DN 150 PN 10/16 5 Boiler house 1400 to 7000 KW
DN 150 PN 10/16 10 Boiler house 1400 to 7000 KW